Faults and Alarms
List of faults and alarms
3-1638
© Siemens AG 2007 All Rights Reserved
SINAMICS S List Manual (LH1), 07/2007
F30897
DRIVE-CLiQ: No communication to component
Drive object:
All objects
Reaction:
A_INFEED: OFF2 (NONE, OFF1)
SERVO: OFF2 (ENCODER, IASC / DCBRAKE, NONE, OFF1, OFF3, STOP1, STOP2)
VECTOR: OFF2 (ENCODER, IASC / DCBRAKE, NONE, OFF1, OFF3, STOP1, STOP2)
Acknowledge:
IMMEDIATELY (POWER ON)
Cause:
Communications with the DRIVE-CLiQ component (power unit) specified by the fault value is not possible.
One cause can be, e.g. that a DRIVE-CLiQ cable has been withdrawn.
Fault value (r0949, interpret decimal):
Component ID.
Remedy:
- check the DRIVE-CLiQ connections.
- carry out a POWER ON.
F30899 (N, A)
Power unit: Unknown fault
Drive object:
All objects
Reaction:
A_INFEED: NONE (OFF1, OFF2)
SERVO: NONE (IASC / DCBRAKE, OFF1, OFF2, OFF3, STOP1, STOP2)
VECTOR: NONE (IASC / DCBRAKE, OFF1, OFF2, OFF3, STOP1, STOP2)
Acknowledge:
IMMEDIATELY (POWER ON)
Cause:
A fault occurred on the power unit that cannot be interpreted by the Control Unit firmware.
This can occur if the firmware on the power unit is more recent than the firmware on the Control Unit.
Fault value (r0949, interpret decimal):
Fault number.
If required, the significance of this new fault can be read about in a more recent description of the Control Unit.
Remedy:
- replace the firmware on the power unit by an older firmware version (r0128).
- upgrade the firmware on the Control Unit (r0018).
Reaction upon N:
NONE
Acknowl. upon N:
NONE
Reaction upon A:
NONE
Acknowl. upon A:
NONE
A30903
Power unit: I2C bus error occurred
Drive object:
All objects
Reaction:
NONE
Acknowledge:
NONE
Cause:
Communications with EPROM not possible.
Fault value (r0949, interpret hexadecimal):
Only for internal Siemens troubleshooting.
Remedy:
Replace the module.
F30907
Power unit: FPGA configuration unsuccessful
Drive object:
A_INF, B_INF, CU_CX32, CU_LINK, CU_S, DMC20, SERVO, S_INF, TB30, TM15, TM15DI_DO, TM17, TM31,
TM41, TM54F_MA, TM54F_SL
Reaction:
A_INFEED: OFF2 (NONE, OFF1)
SERVO: OFF2 (IASC / DCBRAKE, NONE, OFF1, OFF3, STOP1, STOP2)
Acknowledge:
IMMEDIATELY
Cause:
For the initialization within the power unit, an internal software error has occurred.
Remedy:
- replace power unit.
- if required, upgrade the firmware in the power unit.
- contact the Hotline.