![Siemens SINAMICS S Series List Manual Download Page 60](http://html.mh-extra.com/html/siemens/sinamics-s-series/sinamics-s-series_list-manual_1265427060.webp)
Parameters
List of parameters
1-60
© Siemens AG 2007 All Rights Reserved
SINAMICS S List Manual (LH1), 07/2007
Bit 10 = 1 (enable signal missing), if:
- the signal source in p1140 is a 0 signal.
Bit 11 = 1 (enable signal missing) if the velocity setpoint is frozen, because:
- the signal source in p1141 is a 0 signal.
- the velocity setpoint is entered from jogging and the two signal sources for jogging, bit 0 (p1055) and bit 1 (p1056)
have a 1 signal.
Bit 12 = 1 (enable signal missing), if:
- the signal source in p1142 is a 0 signal.
- When activating the function module "basic positioner" (r0108.4 = 1), the signal source in p1142 is set to a 0 sig-
nal.
Bit 16 = 1 (enable signal missing), if:
- there is an OFF1 fault response. The system is only enable if the fault is removed and was acknowledged and the
power-on inhibit withdrawn with OFF1 = 0.
Bit 17 = 1 (enable signal missing), if:
- commissioning mode is selected (p0009 > 0 or p0010 > 0).
- there is an OFF2 fault response.
- the drive is inactive (p0105 = 0) or is not operational (r7850[DO-Index]=0).
Bit 18 = 1 (enable signal missing), if:
- OFF3 has still not be completed or an OFF3 fault response is present.
Bit 19 = 1 (internal pulse enable missing), if:
- synchronization is running between the basic clock cycle, DRIVE-CLiQ clock cycle and application clock cycle.
Bit 20 =1 (internal armature short-circuit active), if:
- the drive is not in the state "S4: Operation" or "S5x" (refer to function chart 2610).
- the internal pulse enable is missing (r0046.19 = 0).
Bit 21 = 1 (enable signal missing), if:
The pulses have been enabled and the velocity setpoint has still not been enabled, because:
- the holding brake opening time (p1216) has still not expired.
- The motor has still not been magnetized (induction motor).
Bit 22: Being prepared
Bit 26 = 1 (enable signal missing), if:
- the drive is inactive (p0105 = 0) or is not operational (r7850[DO-Index]=0).
Bit 27 = 1 (enable signal missing), if:
- de-magnetizing has still not been completed (only for vector).
Bit 28 = 1 (enable signal missing), if:
- the holding brake is closed or has still not been opened.
Bit 29 = 1 (enable signal missing), if:
- the cooling system ready signal via BI: p0266[1] missing.
Bit 30 = 1 (velocity controller inhibited), if one of the following reasons is present:
- A 0 signal is available via BI: p0856.
- the function generator with current input is active.
- the measuring function "current controller reference frequency characteristic" is active.
- the pole position identification is active.
- motor data identification is active (only certain steps).
Bit 31 = 1 (enable missing), if:
- the velocity setpoint from jog 1 or 2 is entered.