Dependency:
Only adjustable if heartbeat time = 0 (heartbeat is disabled).
Refer to: p8606
Note:
For p8604[0] = 0 and/or p8604[1] = 0, the node guarding protocol is not used.
Either node guarding or heartbeat can be used.
Description:
Sets the time [ms] to cyclically send heartbeat telegrams.
The smallest cycle time is 100 ms.
When a 0 is written, then heartbeat telegrams are not sent.
Dependency:
Only adjustable if guard time = 0 (node guarding disabled).
Refer to: p8604
Note:
Corresponds to the CANopen object 1017 hex.
Either node guarding or heartbeat can be used.
Description:
General device information display.
Index:
[0] = Vendor ID
[1] = Product code
[2] = Revision number
[3] = Serial number
Note:
Corresponds to the CANopen object 1018 hex.
Description:
For a bus off error, the CAN bus is restarted with p8608 = 1 after the cause of the error has been removed.
Values:
0:
Inactive
1:
Start CAN controller
Note:
This parameter is automatically reset to 0 after start.
p8606
CBC producer heartbeat time / Prod Heartb Time
CU_S (CAN)
Can be changed:
T
Calculated:
-
Access level:
3
Data type:
Unsigned16
Dynamic index:
-
Func. diagram:
-
P-Group:
-
Units group:
-
Unit selection:
-
Not for motor type:
-
Expert list:
1
Min Max
Factory
setting
0 [ms]
65535 [ms]
0 [ms]
r8607[0...3]
CBC identity object / Identity object
CU_S (CAN)
Can be changed:
-
Calculated:
-
Access level:
3
Data type:
Unsigned32
Dynamic index:
-
Func. diagram:
-
P-Group:
Communications
Units group:
-
Unit selection:
-
Not for motor type:
-
Expert list:
1
Min Max
Factory
setting
- -
-
p8608
CBC clear bus off error / Clear bus off err
CU_S (CAN)
Can be changed:
U, T
Calculated:
-
Access level:
3
Data type:
Integer16
Dynamic index:
-
Func. diagram:
-
P-Group:
-
Units group:
-
Unit selection:
-
Not for motor type:
-
Expert list:
1
Min Max
Factory
setting
0 1
0