![Siemens SINAMICS S Series List Manual Download Page 698](http://html.mh-extra.com/html/siemens/sinamics-s-series/sinamics-s-series_list-manual_1265427698.webp)
Parameters
List of parameters
1-698
© Siemens AG 2007 All Rights Reserved
SINAMICS S List Manual (LH1), 07/2007
Description:
Sets the hysteresis for the "flux outside tolerance" message for the flux monitoring.
Dependency:
Refer to: p3204, p3206
Refer to: F07914
Note:
The monitoring function is only carried out for separately-excited synchronized motors (p0300 = 5).
The flux monitoring is only active after magnetization (r0056.4 = 1).
Description:
Sets the delay time for the "flux outside tolerance" message for the flux monitoring.
Dependency:
Refer to: p3204, p3205
Refer to: F07914
Note:
The monitoring function is only carried out for separately-excited synchronized motors (p0300 = 5).
The flux monitoring is only active after magnetization (r0056.4 = 1).
Description:
Sets the threshold value for the zero current signal for the zero current monitoring.
If the absolute current falls below the threshold value then r2199.6 is set to 1 after the delay time has expired. The
bit is reset if the threshold value and the hysteresis are exceeded again.
Dependency:
Refer to: r2199, p3208, p3209
Note:
The monitoring function is only carried out for separately-excited synchronized motors (p0300 = 5).
The monitoring is only carried out for speeds less than the speed threshold value in p2161 (r2199.0 = 1).
Description:
Sets the hysteresis for the zero current signal for the zero current monitoring.
Dependency:
Refer to: p3207, p3209
p3205[0...n]
Flux outside the tolerance hysteresis / Flux n. tol hyst
VECTOR
Can be changed:
U, T
Calculated:
-
Access level:
3
Data type:
Floating Point
Dynamic index:
DDS, p0180
Func. diagram:
-
P-Group:
Messages
Units group:
-
Unit selection:
-
Not for motor type:
ASM, PEM, REL
Expert list:
1
Min Max
Factory
setting
0.1 [%]
50.0 [%]
10.0 [%]
p3206[0...n]
Flux outside tolerance delay time / Flux n. tol t_del
VECTOR
Can be changed:
U, T
Calculated:
-
Access level:
3
Data type:
Floating Point
Dynamic index:
DDS, p0180
Func. diagram:
-
P-Group:
Messages
Units group:
-
Unit selection:
-
Not for motor type:
ASM, PEM, REL
Expert list:
1
Min Max
Factory
setting
0.0 [s]
10.0 [s]
5.0 [s]
p3207[0...n]
Zero current signal threshold value / I_0_sig thresh
VECTOR
Can be changed:
U, T
Calculated:
CALC_MOD_LIM_REF
Access level:
3
Data type:
Floating Point
Dynamic index:
DDS, p0180
Func. diagram:
-
P-Group:
Messages
Units group:
6_2
Unit selection:
p0505
Not for motor type:
ASM, PEM, REL
Expert list:
1
Min Max
Factory
setting
0.01 [Arms]
10000.00 [Arms]
1.00 [Arms]
p3208[0...n]
Zero current signal hysteresis / I_0_sig hyst
VECTOR
Can be changed:
U, T
Calculated:
CALC_MOD_LIM_REF
Access level:
3
Data type:
Floating Point
Dynamic index:
DDS, p0180
Func. diagram:
-
P-Group:
Messages
Units group:
6_2
Unit selection:
p0505
Not for motor type:
ASM, PEM, REL
Expert list:
1
Min Max
Factory
setting
0.01 [Arms]
10000.00 [Arms]
1.00 [Arms]