Parameters
List of parameters
1-324
© Siemens AG 2007 All Rights Reserved
SINAMICS S List Manual (LH1), 07/2007
Description:
Sets the signal source for control word 1 bit 6 (enables setpoint/disable setpoint).
Dependency:
Refer to: p1140, p1141
Notice:
The parameter may be protected as a result of p0922 or p2079 and cannot be changed.
Note:
Bit 6 = 0: Inhibits the setpoint (the ramp-function generator input is set to zero)
Bit 6 = 1: Enable setpoint
Description:
Sets the signal source for control word 1 bit 6 (enables setpoint/disable setpoint).
Dependency:
Refer to: p1140, p1141
Notice:
The parameter may be protected as a result of p0922 or p2079 and cannot be changed.
Note:
Bit 6 = 0: Inhibits the setpoint (the ramp-function generator input is set to zero)
Bit 6 = 1: Enable setpoint
Description:
Sets the signal source for accepting the setting value of the ramp-function generator.
Dependency:
The signal source for the ramp-function generator setting value is set using parameters.
Refer to: p1144
Note:
0/1 signal:
The ramp-function generator output is immediately (without delay) set to the setting value of the ramp-function gen-
erator.
1 signal:
The setting value of the ramp-function generator is effective.
1/0 signal:
The input value of the ramp-function generator is effective. The ramp-function generator output is adapted to the
input value using the ramp-up time or the ramp-down time.
0 signal:
The input value of the ramp-function generator is effective.
p1142[0...n]
BI: Enable velocity setpoint / Enable v_set
SERVO (Lin)
Can be changed:
T
Calculated:
-
Access level:
3
Data type:
Unsigned32 / Binary
Dynamic index:
CDS, p0170
Func. diagram:
2441, 2442,
2443, 2501, 2711
P-Group:
Setpoints
Units group:
-
Unit selection:
-
Not for motor type:
-
Expert list:
1
Min Max
Factory
setting
- -
1
p1142
BI: Enable speed setpoint / Enable n_set
TM41
Can be changed:
T
Calculated:
-
Access level:
3
Data type:
Unsigned32 / Binary
Dynamic index:
-
Func. diagram:
9674
P-Group:
Setpoints
Units group:
-
Unit selection:
-
Not for motor type:
-
Expert list:
1
Min Max
Factory
setting
- -
1
p1143[0...n]
BI: Ramp-function generator, accept setting value / Accept RFG set val
SERVO (Extended
setp), VECTOR
Can be changed:
T
Calculated:
-
Access level:
3
Data type:
Unsigned32 / Binary
Dynamic index:
CDS, p0170
Func. diagram:
3070
P-Group:
Setpoints
Units group:
-
Unit selection:
-
Not for motor type:
-
Expert list:
1
Min Max
Factory
setting
- -
0