Parameters
List of parameters
1-534
© Siemens AG 2007 All Rights Reserved
SINAMICS S List Manual (LH1), 07/2007
Description:
Sets the additional monitoring time to monitor the process data received via PROFIBUS.
If no process data is received within this time, an appropriate message is output.
Dependency:
Refer to: F01910
Description:
Sets the sampling time for the cyclic interface 1 (IF1).
Note:
For clock cycle synchronous operation, the specified bus cycle time applies (Tdp).
Description:
Connector output to interconnect PZD (setpoints) with word format received from the PROFIBUS master.
Index:
[0] = PZD 1
[1] = PZD 2
[2] = PZD 3
[3] = PZD 4
[4] = PZD 5
Note:
IF1: Interface 1
Description:
Connector output to interconnect PZD (setpoints) with word format received from the PROFIBUS master.
Index:
[0] = PZD 1
[1] = PZD 2
[2] = PZD 3
[3] = PZD 4
[4] = PZD 5
[5] = PZD 6
[6] = PZD 7
[7] = PZD 8
p2047
PROFIBUS additional monitoring time / PB suppl t_monit
CU_S
Can be changed:
U, T
Calculated:
-
Access level:
3
Data type:
Floating Point
Dynamic index:
-
Func. diagram:
2410
P-Group:
Communications
Units group:
-
Unit selection:
-
Not for motor type:
-
Expert list:
1
Min Max
Factory
setting
0 [ms]
2000 [ms]
0 [ms]
p2048
IF1 PROFIdrive PZD sampling time / IF1 PZD t_sample
CU_CX32, CU_S
Can be changed:
C1(3)
Calculated:
-
Access level:
3
Data type:
Floating Point
Dynamic index:
-
Func. diagram:
-
P-Group:
Communications
Units group:
-
Unit selection:
-
Not for motor type:
-
Expert list:
1
Min Max
Factory
setting
1.00 [ms]
16.00 [ms]
4.00 [ms]
r2050[0...4]
CO: IF1 PROFIdrive PZD receive word / IF1 PZD recv word
A_INF, B_INF,
CU_CX32, CU_S,
S_INF, TB30,
TM15DI_DO, TM31
Can be changed:
-
Calculated:
-
Access level:
3
Data type:
Integer16
Dynamic index:
-
Func. diagram:
-
P-Group:
Communications
Units group:
-
Unit selection:
-
Not for motor type:
-
Expert list:
1
Min Max
Factory
setting
- -
-
r2050[0...15]
CO: IF1 PROFIdrive PZD receive word / IF1 PZD recv word
SERVO, TM41
Can be changed:
-
Calculated:
-
Access level:
3
Data type:
Integer16
Dynamic index:
-
Func. diagram:
2440, 2460
P-Group:
Communications
Units group:
-
Unit selection:
-
Not for motor type:
-
Expert list:
1
Min Max
Factory
setting
- -
-