List of parameters
Parameters
1-797
© Siemens AG 2007 All Rights Reserved
SINAMICS S List Manual (LH1), 07/2007
Values:
0:
Unipolar voltage input (0 V ... +10 V)
2:
Unipolar current input (0 mA ... +20 mA)
3:
Unipolar current input monitored (4 mA ... +20 mA)
4:
Bipolar voltage input (-10 V ... +10 V)
5:
Bipolar current input (-20 mA ... +20 mA)
Index:
[0] = AI 0 (X521.1/X521.2, S5.0)
[1] = AI 1 (X521.3/X521.4, S5.1)
Warning:
The maximum voltage difference between the analog input terminals AI+, AI- and the ground of the TM31 (X520.6,
X530.3) may not exceed 35 V.
For operation with the load resistor switched-in, the voltage between the differential inputs AI+ and AI- may not
exceed 15 V or the impressed current of 60 mA; if this is not carefully observed, the input will be damaged.
Notice:
For use as voltage input, switch S500 must be set to 0 for the input involved.
Switch S500 is located on the front panel of the TM31 above terminal block X521.
Note:
When changing p4056, the parameters of the normalization characteristic (p4057, p4058, p4059, p4060) are over-
written with the following default values:
For p4056 = 0, 4, p4057 is set to 0.0 V, p4058 to 0.0 %, p4059 to 10.0 V and p4060 to 100.0 %.
For p4056 = 2, 5, p4057 is set to 0.0 mA, p4058 to 0.0 %, p4059 to 20.0 mA and p4060 to 100.0 %.
For p4056 = 3, p4057 is set to 4.0 mA, p4058 to 0.0 %, p4059 to 20.0 mA and p4060 to 100.0 %.
Description:
Displays the type of the analog input.
Values:
4:
Bipolar voltage input (-10 V ... +10 V)
Description:
Sets the normalization characteristic for the analog inputs of Terminal Board 30 (TB30).
The normalization characteristic for the analog inputs is defined using two points.
This parameter specifies the x coordinate (input voltage in V) of the 1st value pair of the characteristic.
Index:
[0] = AI 0 (X482.1/X482.2)
[1] = AI 1 (X482.3/X482.4)
Note:
The parameters for the characteristic do not limit.
Description:
Sets the normalization characteristic for the analog inputs of terminal module 31 (TM31).
The normalization characteristic for the analog inputs is defined using two points.
r4056
TM41 analog input, type / TM41 AI type
TM41
Can be changed:
-
Calculated:
-
Access level:
1
Data type:
Integer16
Dynamic index:
-
Func. diagram:
-
P-Group:
Terminals
Units group:
-
Unit selection:
-
Not for motor type:
-
Expert list:
1
Min Max
Factory
setting
4 4
-
p4057[0...1]
TB30 analog inputs, characteristic value x1 / TB30 AI char x1
TB30
Can be changed:
U, T
Calculated:
-
Access level:
2
Data type:
Floating Point
Dynamic index:
-
Func. diagram:
9104
P-Group:
Terminals
Units group:
-
Unit selection:
-
Not for motor type:
-
Expert list:
1
Min Max
Factory
setting
-11.000 [V]
11.000 [V]
0.000 [V]
p4057[0...1]
TM31 analog inputs, characteristic value x1 / TM31 AI char x1
TM31
Can be changed:
U, T
Calculated:
-
Access level:
2
Data type:
Floating Point
Dynamic index:
-
Func. diagram:
9566, 9568
P-Group:
Terminals
Units group:
-
Unit selection:
-
Not for motor type:
-
Expert list:
1
Min Max
Factory
setting
-20.000 20.000
0.000