Parameters
List of parameters
1-496
© Siemens AG 2007 All Rights Reserved
SINAMICS S List Manual (LH1), 07/2007
Dependency:
"Quick commissioning" must be carried out (p0010 = 1) before executing the motor data identification routine!
In the simulation mode, the parameter cannot be written into. When selecting the motor data identification routine,
the drive data set changeover is suppressed.
Refer to: p1272, p1900
Caution:
After the motor data identification (p1910 > 0) has been selected, alarm A07991 is output and a motor data identifi-
cation routine is carried out as follows at the next power-on command:
- current flows through the motor and a voltage is present at the drive converter output terminals.
- during the identification routine, the motor shaft can rotate through a maximum of half a revolution.
- however, no torque torque is generated.
Notice:
In order to permanently accept the determined settings they must be saved in a non-volatile fashion (p0971,
p0977).
Note:
When setting p1910, the following should be observed:
1. "With transfer" means:
The parameters specified in the description are overwritten with the identified values and therefore have an influ-
ence on the controller setting.
2. "Without transfer" means:
The identified parameters are only displayed in the range r1912 ... r1926. The controller settings remain
unchanged.
Description:
Sets the number of phases to be identified.
Values:
1:
1 phase U
2:
2 phases U, V
3:
3 phases U, V, W
Note:
When identifying with several phases, the accuracy increases and also the time it takes to make the measurement.
Description:
Displays the identified stator resistance.
Dependency:
Refer to: p1909, p1910, r1913, r1915, r1925, r1927, r1932, r1933, r1934, r1935, r1936, r1950, r1951, p1952,
p1953
Description:
Displays the identified stator resistance.
p1911
Number of phases to be identified / Qty ph to ident
VECTOR
Can be changed:
T
Calculated:
-
Access level:
4
Data type:
Integer16
Dynamic index:
-
Func. diagram:
-
P-Group:
Motor identification
Units group:
-
Unit selection:
-
Not for motor type:
-
Expert list:
1
Min Max
Factory
setting
1 3
1
r1912
Stator resistance identified / R_stator ident
SERVO
Can be changed:
-
Calculated:
-
Access level:
3
Data type:
Floating Point
Dynamic index:
-
Func. diagram:
-
P-Group:
Motor identification
Units group:
-
Unit selection:
-
Not for motor type:
-
Expert list:
1
Min Max
Factory
setting
- [Ohm]
- [Ohm]
- [Ohm]
r1912[0...2]
Identified stator resistance / R_stator ident
VECTOR
Can be changed:
-
Calculated:
-
Access level:
4
Data type:
Floating Point
Dynamic index:
-
Func. diagram:
-
P-Group:
Motor identification
Units group:
-
Unit selection:
-
Not for motor type:
-
Expert list:
1
Min Max
Factory
setting
- [Ohm]
- [Ohm]
- [Ohm]