Parameters
List of parameters
1-472
© Siemens AG 2007 All Rights Reserved
SINAMICS S List Manual (LH1), 07/2007
Description:
Sets the fault threshold in order to detect a motor that has stalled.
If the error signal (r1746) exceeds the parameterized error threshold, then bit 12 in status word p1408 is set.
Dependency:
If a stalled drive is detected (p1408.12 set), fault 7902 is output after the delay time set in p2178.
Refer to: p2178
Note:
Monitoring is only effective in the low-speed range (below p1755 * (100% - p1756)).
Description:
Signal to initiate stall detection
Note:
The signal is not calculated while magnetizing and only in the low speed range (below p1755 * (100 % - p1756)).
Description:
Sets the configuration of the motor model.
Note:
Bit 4:
The time-controlled motor changeover is only effective for vector control with encoder.
Description:
Displays the status of the motor model.
p1745[0...n]
Motor model error threshold stall detection / MotMod ThreshStall
VECTOR (n/M)
Can be changed:
U, T
Calculated:
CALC_MOD_REG
Access level:
3
Data type:
Floating Point
Dynamic index:
DDS, p0180
Func. diagram:
-
P-Group:
Closed-loop control
Units group:
-
Unit selection:
-
Not for motor type:
-
Expert list:
1
Min Max
Factory
setting
0.0 [%]
1000.0 [%]
5.0 [%]
r1746
Motor model error signal stall detection / MotMod sig stall
VECTOR (n/M)
Can be changed:
-
Calculated:
-
Access level:
4
Data type:
Floating Point
Dynamic index:
-
Func. diagram:
-
P-Group:
Closed-loop control
Units group:
-
Unit selection:
-
Not for motor type:
PEM, REL
Expert list:
1
Min Max
Factory
setting
- [%]
- [%]
- [%]
p1750[0...n]
Motor model configuration / MotMod config
VECTOR (n/M)
Can be changed:
U, T
Calculated:
-
Access level:
3
Data type:
Unsigned8
Dynamic index:
DDS, p0180
Func. diagram:
-
P-Group:
Closed-loop control
Units group:
-
Unit selection:
-
Not for motor type:
PEM, REL, FEM
Expert list:
1
Min Max
Factory
setting
- -
0000
bin
Bit field:
Bit
Signal name
1 signal
0 signal
FP
00
Controlled start
Yes
No
-
01
Controlled through 0 Hz
Yes
No
-
02
Maintain closed-loop control operation for
sufficient mot load
Yes
No
-
03
Motor model Lh_pre=f(PsiEst)
Yes
No
-
04
Model changeover
time controlled
freq controlled
-
r1751
Motor model status / MotMod status
VECTOR (n/M)
Can be changed:
-
Calculated:
-
Access level:
3
Data type:
Unsigned16
Dynamic index:
-
Func. diagram:
-
P-Group:
Closed-loop control
Units group:
-
Unit selection:
-
Not for motor type:
PEM, REL, FEM
Expert list:
1
Min Max
Factory
setting
- -
-