512
System Configuration and Wiring
Section 11-2
10) Trial Operation (Operation Check)
Note
A simple explanation of the operation procedure is given below. For details,
refer to the
CX-Motion Online Help
.
Use the following procedures to confirm correct operation of the MC program
in Automatic Mode and servo-lock, origin search and jogging operations in
Manual Mode.
Manual Mode
Power ON
If power is supplied to the MC Unit when the Servo Driver alarm input is
already ON, an error will not be generated. An error will occur, however, if the
alarm turns OFF and then ON again, or if an instruction that includes axis
operation is performed with the alarm still ON. This feature allows greater flex-
ibility with the sequence in which power is supplied to the MC Unit and the
Servo Drive.
When operating the MC Unit online form a personal computer, the power sup-
ply for the personal computer must be ON first. Otherwise an error will occur.
MC Coordinate Displays
Display the MC coordinates in order to check the present position of each
axis.
1,2,3...
1.
Select
Online/MC coordinate display
.
2.
Click
Start
.
Servo-lock
Set the Automatic/Manual switch to Manual. Servo-lock the X and Y axes by
pressing the Operation Buttons. By performing servo-lock, power will be sup-
plied to each axis. While the servo is locked, the CW and CCW indicators will
flash. On the MC coordinates display screen, the present position values and
the error counter pulse numbers will constantly change in a neighborhood of
0.
Origin Search
Set the Automatic/Manual switch to Manual. Execute an origin search for the
X and Y axes by pressing the Origin Buttons. The axes will move to the origin.
When origin search has been completed, the reference coordinate system
Summary of Contents for CS1W-MC221 -
Page 1: ...Motion Control Units Cat No W359 E1 04 CS1W MC221 V1 421 V1 OPERATION MANUAL ...
Page 2: ...CS1W MC221 V1 421 V1 Motion Control Units Operation Manual Revised February 2008 ...
Page 3: ...iv ...
Page 5: ...vi ...
Page 11: ...xii ...
Page 15: ...xvi ...
Page 19: ...xx ...
Page 27: ...xxviii Conformance to EC Directives 6 ...
Page 133: ...106 Installation Section 2 2 2 2 4 Dimensions CS1W MC421 CS1W MC221 ...
Page 173: ...146 Connecting Peripheral Devices Section 2 7 ...
Page 227: ...200 Command Area Section 3 6 ...
Page 351: ...324 Interface Specifics Section 5 4 ...
Page 513: ...486 Absolute Encoder Interface Specifications Section 9 7 ...
Page 575: ...548 Error Log Section 12 6 ...
Page 589: ...562 Performance Appendix A ...
Page 655: ...628 Control Bit Flag Timing Charts Appendix E ...
Page 683: ...656 Origin Search Patterns Appendix F ...
Page 685: ...658 Encoder Divider Rate and Rotation Speed for OMRON Servo Drivers Appendix G ...