16 - 26
Chapter 16 Troubleshooting
Classification
of errors
Error
code
Error name
Error
Operation status at error occurrence
Positioning
operation
errors
514
Outside new current
value range
The new current address is outside the
ranges of 0 to 359.99999, where the
control unit is set to "degree".
Current value is not changed.
515
New current value not
possible
• The control method sets an operation
pattern (continuous path control) using
new current positioning data.
• The operation pattern sets a "new current
value" in the control method using the
data following the "continuous path
control" positioning data.
516
Continuous path
control not possible
• The continuous path control is designated
using a control method which is not
allowed to use for continuous path control
such as speed control, speed-position
switching control, position-speed
switching control, fixed-feed, and current
value changing.
• The previous data such as those on
speed control, speed-position switching
control, position-speed switching control,
fixed-feed, and current value changing
shows a continuous path control.
• The continuous positioning control is
designated for speed control or position-
speed switching control.
The system does not operate at start.
518
Outside operation
pattern range
The operation pattern set value is 2.
At start
: The system does not
operate.
During operation : The system stops with the
setting (deceleration
stop/sudden stop) of the
detailed parameter 2
Sudden stop selection
(stop group 3).
(Note that the deceleration
stop only occurs during the
manual pulse generator
operation.)
519
Interpolation while
interpolation axis BUSY
Interpolation is started during the operation
of the interpolation axis.
520 Unit group unmatched
The reference and interpolation axis units
are different at the parameter "interpolation
speed designation method" setting of
"composite speed".
521
Illegal interpolation
description command
In 2-axis interpolation, the axis to be
interpolated is the self axis or an axis not
present.
522
Command speed
setting error
The command speed is outside the setting
range.
Linear interpolation, circular interpolation:
Reference axis is outside the setting
range.
Speed control interpolation:
Either of reference axis and interpolation
axis is outside the speed range.
Summary of Contents for MELSEC-L Series
Page 2: ......
Page 30: ...MEMO ...
Page 70: ...2 10 Chapter 2 System Configuration MEMO ...
Page 83: ...3 13 Chapter 3 Specifications and Functions MEMO ...
Page 103: ...3 33 Chapter 3 Specifications and Functions MEMO ...
Page 107: ...3 37 Chapter 3 Specifications and Functions MEMO ...
Page 111: ...3 41 Chapter 3 Specifications and Functions MEMO ...
Page 115: ...3 45 Chapter 3 Specifications and Functions MEMO ...
Page 140: ...4 22 Chapter 4 Installation Wiring and Maintenance of the Product MEMO ...
Page 253: ...5 113 Chapter 5 Data Used for Positioning Control MEMO ...
Page 342: ...5 202 Chapter 5 Data Used for Positioning Control MEMO ...
Page 438: ...7 20 Chapter 7 Memory Configuration and Data Process MEMO ...
Page 440: ...MEMO ...
Page 485: ...9 25 Chapter 9 Major Positioning Control MEMO ...
Page 594: ...9 134 Chapter 9 Major Positioning Control MEMO ...
Page 624: ...10 30 Chapter 10 High Level Positioning Control MEMO ...
Page 656: ...11 32 Chapter 11 Manual Control MEMO ...
Page 690: ...12 34 Chapter 12 Expansion Control MEMO ...
Page 798: ...13 108 Chapter 13 Control Sub Functions MEMO ...
Page 866: ...14 68 Chapter 14 Common Functions MEMO ...
Page 884: ...15 18 Chapter 15 Dedicated Instructions MEMO ...
Page 899: ...16 15 Chapter 16 Troubleshooting MEMO ...
Page 1036: ...Appendix 88 Appendices MEMO ...
Page 1039: ......