![LEGRAND Raritan SRC-0100 User Manual Download Page 514](http://html1.mh-extra.com/html/legrand/raritan-src-0100/raritan-src-0100_user-manual_1870928514.webp)
Chapter 8: Using the Command Line Interface
502
Example - Default Upper Thresholds for Temperature
It is assumed that your preferred measurement unit for temperature is
set to degrees Celsius. Then the following command sets the default
Upper Warning threshold to 20
and Upper Critical threshold to 24
for all temperature sensors.
config:#
defaultThresholds temperature upperWarning 20
upperCritical 24
Environmental Sensor Threshold Configuration Commands
You can use the sensor threshold configuration commands to set the
threshold, hysteresis and assertion timeout values for any environmental
sensor.
It is permitted to assign a new value to the threshold at any time
regardless of whether the threshold has been enabled.
Threshold Configuration Commands for a Sensor
A sensor threshold configuration command for environmental sensors
begins with
sensor externalsensor.
You can configure various environmental sensor threshold settings at a
time by combining multiple commands. See
Multi-Command Syntax
(on
page 517).
Set the Upper Critical threshold for an environmental sensor:
config:#
sensor externalsensor <n> <sensor type> upperCritical <option>
Set the Upper Warning threshold for an environmental sensor:
config:#
sensor externalsensor <n> <sensor type> upperWarning <option>
Set the Lower Critical threshold for an environmental sensor:
config:#
sensor externalsensor <n> <sensor type> lowerCritical <option>
Set the Lower Warning threshold for an environmental sensor:
Summary of Contents for Raritan SRC-0100
Page 114: ...Chapter 6 Using the Web Interface 102...
Page 291: ...Chapter 6 Using the Web Interface 279...
Page 301: ...Chapter 6 Using the Web Interface 289 6 Click Create to finish the creation...
Page 311: ...Chapter 6 Using the Web Interface 299...
Page 312: ...Chapter 6 Using the Web Interface 300 Continued...
Page 625: ...Appendix H RADIUS Configuration Illustration 613 Note If your SRC uses PAP then select PAP...
Page 630: ...Appendix H RADIUS Configuration Illustration 618 14 The new attribute is added Click OK...
Page 631: ...Appendix H RADIUS Configuration Illustration 619 15 Click Next to continue...