Chapter 6: Using the Web Interface
273
4.
To select the actuator(s) where this action will be applied, select
them one by one from the 'Available actuators' list.
To add all actuators, click Select All.
5.
To remove any selected actuator from the 'Selected actuators' field,
click that actuator's
.
To remove all actuators, click Deselect All.
Syslog Message
Use this action to automatically forward event messages to the specified
syslog server. Determine the syslog transmission mechanism you prefer
when setting it up - UDP, TCP or TLS over TCP.
SRC may or may not detect the syslog message transmission failure. If
yes, it will log this syslog failure as well as the failure reason in the event
log. See
Viewing or Clearing the Local Event Log
(on page 325).
Operation:
1.
Choose Device Settings > Event Rules >
.
2.
Select 'Syslog message' from the Action list.
3.
In the 'Syslog server' field, specify the IP address to which the syslog
is forwarded.
4.
In the 'Transport protocol' field, select one of the syslog protocols:
TCP, UDP or TCP+TLS. The default is UDP.
Transport
protocols
Next steps
UDP
In the 'UDP port' field, type an appropriate port number. Default is 514.
Select the 'Legacy BSD syslog protocol' checkbox if applicable.
TCP
NO TLS certificate is required. Type an appropriate port number in the 'TCP port' field.
Summary of Contents for Raritan SRC-0100
Page 114: ...Chapter 6 Using the Web Interface 102...
Page 291: ...Chapter 6 Using the Web Interface 279...
Page 301: ...Chapter 6 Using the Web Interface 289 6 Click Create to finish the creation...
Page 311: ...Chapter 6 Using the Web Interface 299...
Page 312: ...Chapter 6 Using the Web Interface 300 Continued...
Page 625: ...Appendix H RADIUS Configuration Illustration 613 Note If your SRC uses PAP then select PAP...
Page 630: ...Appendix H RADIUS Configuration Illustration 618 14 The new attribute is added Click OK...
Page 631: ...Appendix H RADIUS Configuration Illustration 619 15 Click Next to continue...