Appendix I: Additional SRC Information
650
In the threshold settings, the Deassertion Hysteresis field determines a
new level to trigger the "deassertion" action.
This function is similar to a thermostat, which instructs the air
conditioner to turn on the cooling system when the temperature exceeds
a pre-determined level. "Deassertion Hysteresis" instructs the SRC to
de-assert the worse state for a sensor only when that sensor's reading
reaches the pre-determined "deassertion" level.
For upper thresholds, this "deassertion" level is a decrease against each
threshold. For lower thresholds, this level is an increase to each
threshold. The absolute value of the decrease/increase is exactly the
hysteresis value.
For example, if Deassertion Hysteresis = 2, then the deassertion level of
each threshold is either "+2" or "-2" as illustrated below.
Threshold value
Deassertion value
Upper Critical = 33
Deassertion level = 31
33 - 2 = 31
Upper Warning = 25
Deassertion level = 23
25 - 2 = 23
Lower Critical = 10
Deassertion level = 12
10 + 2 = 12
Lower Warning = 18
Deassertion level = 20
18 + 2 = 20
To use each threshold as the "deassertion" level instead of determining
a new level, set the Deassertion Hysteresis to 0 (zero).
Note: The difference between Upper Warning and Lower Warning must
be at least "two times" of the deassertion value.
How "Deassertion Hysteresis" is helpful:
If you have created an event rule that instructs the SRC to send
notifications for deassertion events, setting the "Deassertion Hysteresis"
is helpful for eliminating a number of notifications that you may receive
in case a sensor's readings fluctuate around a certain threshold.
Deassertion Hysteresis Example for Temperature Sensors
Summary of Contents for Raritan SRC-0100
Page 114: ...Chapter 6 Using the Web Interface 102...
Page 291: ...Chapter 6 Using the Web Interface 279...
Page 301: ...Chapter 6 Using the Web Interface 289 6 Click Create to finish the creation...
Page 311: ...Chapter 6 Using the Web Interface 299...
Page 312: ...Chapter 6 Using the Web Interface 300 Continued...
Page 625: ...Appendix H RADIUS Configuration Illustration 613 Note If your SRC uses PAP then select PAP...
Page 630: ...Appendix H RADIUS Configuration Illustration 618 14 The new attribute is added Click OK...
Page 631: ...Appendix H RADIUS Configuration Illustration 619 15 Click Next to continue...