Chapter 8: Using the Command Line Interface
501
config:#
defaultThresholds <sensor type> assertionTimeout <as_value>
Variables:
<sensor type> is one of the following numeric sensor types:
Sensor types
Description
absoluteHumidity
Absolute humidity sensors
relativeHumidity Relative
humidity
sensors
temperature Temperature
sensors
airPressure Air
pressure
sensors
airFlow
Air flow sensors
vibration Vibration
sensors
<value> is the value for the specified threshold of the specified
sensor type. Note that diverse sensor types use different
measurement units.
Sensor types
Measurement units
absoluteHumidity
g/m^3 (that is, g/m
3
)
relativeHumidity %
temperature
Degrees Celsius (
) or Fahrenheit (
),
depending on your measurement unit settings.
airPressure
Pascal (Pa) or psi, depending on your
measurement unit settings.
airFlow m/s
vibration g
<hy_value> is the deassertion hysteresis value applied to the
specified sensor type.
<as_value> is the assertion timeout value applied to the specified
sensor type. It ranges from 0 to 100 (samples).
Summary of Contents for Raritan SRC-0100
Page 114: ...Chapter 6 Using the Web Interface 102...
Page 291: ...Chapter 6 Using the Web Interface 279...
Page 301: ...Chapter 6 Using the Web Interface 289 6 Click Create to finish the creation...
Page 311: ...Chapter 6 Using the Web Interface 299...
Page 312: ...Chapter 6 Using the Web Interface 300 Continued...
Page 625: ...Appendix H RADIUS Configuration Illustration 613 Note If your SRC uses PAP then select PAP...
Page 630: ...Appendix H RADIUS Configuration Illustration 618 14 The new attribute is added Click OK...
Page 631: ...Appendix H RADIUS Configuration Illustration 619 15 Click Next to continue...