Appendix J: Additional PX3TS Information
848
Tip: To determine which PX3TS may be the failure point of network, you may
ping each PX3TS in the cascading chain, or check the slave-related events in the
event log of each PX3TS. See
The Ping Tool
(on page 849) and
Slave Device
Events in the Log
(on page 848).
For a cascading chain comprising only products with "dual" Ethernet
ports, also check the following:
•
Whether the Ethernet interface (ETH1 or ETH2) where the network or
cascading cable is connected is disabled on the cascaded device in
question or any upstream device.
•
Whether the connection complies with the cascading guidelines, when set
to the Port Forwarding mode. See
Restrictions of Port-Forwarding
Connections
(on page 34).
•
Whether a newer product model, if involved in the chain, runs the
appropriate minimum firmware version or later.
Slave Device Events in the Log
The log messages for connection/disconnection of a cascaded device are
different for USB-cascading and Ethernet-cascading chains.
Messages for the Ethernet-cascading chain:
Whenever the connection or disconnection of a master/slave device is
detected, both PX3TS devices connected via that network cable record this
event in their internal logs.
There are two slave-related events:
Event
Description
The ETH1/2 network interface
link is now up.
This log entry is generated when the PX3TS
detects the connection of the upstream or
downstream cascaded device on one of its
Ethernet ports.
The ETH1/2 network interface
link is now down.
This log entry is generated when the PX3TS
detects the disconnection of the upstream
or downstream cascaded device on one of
its Ethernet ports.
Содержание Raritan PX3TS
Страница 4: ......
Страница 6: ......
Страница 20: ......
Страница 52: ...Chapter 3 Initial Installation and Configuration 32 Number Device role Master device Slave 1 Slave 2 Slave 3...
Страница 80: ...Chapter 4 Connecting External Equipment Optional 60...
Страница 109: ...Chapter 5 PDU Linking 89...
Страница 117: ...Chapter 5 PDU Linking 97...
Страница 440: ...Chapter 7 Using the Web Interface 420 If wanted you can customize the subject and content of this email in this action...
Страница 441: ...Chapter 7 Using the Web Interface 421...
Страница 464: ...Chapter 7 Using the Web Interface 444...
Страница 465: ...Chapter 7 Using the Web Interface 445 Continued...
Страница 746: ...Appendix A Specifications 726...
Страница 823: ...Appendix I RADIUS Configuration Illustration 803 Note If your PX3TS uses PAP then select PAP...
Страница 824: ...Appendix I RADIUS Configuration Illustration 804 10 Select Standard to the left of the dialog and then click Add...
Страница 825: ...Appendix I RADIUS Configuration Illustration 805 11 Select Filter Id from the list of attributes and click Add...
Страница 828: ...Appendix I RADIUS Configuration Illustration 808 14 The new attribute is added Click OK...
Страница 829: ...Appendix I RADIUS Configuration Illustration 809 15 Click Next to continue...
Страница 860: ...Appendix J Additional PX3TS Information 840...
Страница 890: ...Appendix K Integration 870 3 Click OK...
Страница 900: ......