Chapter 7: Using the Web Interface
212
PX3TS Latching Relay Behavior
PX3TS incorporates latching relays in models with outlet switching. Unlike
non-latching relays, latching relays do NOT require power to keep their
contacts closed.
PX3TS outlet switching can be configured to operate as a true latching relay or
to simulate a non-latching relay. The operating mode determines the latching
relay behavior when PDU power is lost. Regardless of which mode is selected,
power is not required to keep relay contacts closed.
Non-Latching Mode:
•
Relay always opens when power is lost. This insures all relays are open
when power is applied to the PDU.
•
Always select this mode if the combined in-rush current of the devices
connected to the PDU trip circuit breakers when power is applied to the
PDU.
•
This is the factory default operating mode.
Latching Mode:
•
Relay does not open when power is lost.
•
This is the preferred operating mode ONLY if you are sure in-rush current
does not trip circuit breakers when power is applied to the PDU.
•
Power to the outlet is not disrupted if a PDU internal failure occurs.
•
In Latching mode, the following features are disabled.
▪
PDU-level outlet state on startup: See
PDU
(on page 206).
▪
Outlet-level outlet state on startup: See
Individual Outlet Pages
(on
page 232).
▪
PDU-level outlet initialization delay on startup: See
PDU
(on page 206).
Options for Outlet State on Startup
The following are available options for initial power states of outlets after
powering up the PX3TS device.
Option
Function
on
Turns on the outlet(s).
off
Turns off the outlet(s).
last known
Restores the outlet(s) to the previous power state(s)
before the PX3TS was powered off.
If you are configuring an individual outlet on
Individual Outlet Pages
(on page
232), there is one more outlet state option.
Содержание Raritan PX3TS
Страница 4: ......
Страница 6: ......
Страница 20: ......
Страница 52: ...Chapter 3 Initial Installation and Configuration 32 Number Device role Master device Slave 1 Slave 2 Slave 3...
Страница 80: ...Chapter 4 Connecting External Equipment Optional 60...
Страница 109: ...Chapter 5 PDU Linking 89...
Страница 117: ...Chapter 5 PDU Linking 97...
Страница 440: ...Chapter 7 Using the Web Interface 420 If wanted you can customize the subject and content of this email in this action...
Страница 441: ...Chapter 7 Using the Web Interface 421...
Страница 464: ...Chapter 7 Using the Web Interface 444...
Страница 465: ...Chapter 7 Using the Web Interface 445 Continued...
Страница 746: ...Appendix A Specifications 726...
Страница 823: ...Appendix I RADIUS Configuration Illustration 803 Note If your PX3TS uses PAP then select PAP...
Страница 824: ...Appendix I RADIUS Configuration Illustration 804 10 Select Standard to the left of the dialog and then click Add...
Страница 825: ...Appendix I RADIUS Configuration Illustration 805 11 Select Filter Id from the list of attributes and click Add...
Страница 828: ...Appendix I RADIUS Configuration Illustration 808 14 The new attribute is added Click OK...
Страница 829: ...Appendix I RADIUS Configuration Illustration 809 15 Click Next to continue...
Страница 860: ...Appendix J Additional PX3TS Information 840...
Страница 890: ...Appendix K Integration 870 3 Click OK...
Страница 900: ......