99
Common Parameter Area
Section 4-3
Check Error (Unit error code 0028) will occur when the PCU power is
turned ON or the Unit is restarted.
(4) Do not set the bank number of the EM Area that is being saved to file
memory in the CPU Unit. When the EM Area for the bank saved to file
memory has been specified, the information in the Operating Data Area
will not be reflected, resulting in a malfunction. If multiple PCUs are
mounted to a single PLC, make sure that the Operating Data Areas do
not overlap. The PCU will not detect an error if the Operating Data Areas
overlap, which may result in a malfunction.
Setting Example
Details
Refer to
6-2-2 Scan List and PCU Area Allocations
.
CIO 100
CIO 125
CIO 500
CIO 525
1838 hex
00B0 (hex)
1839 hex
0064 (hex)
183A (hex) 00B0 (hex)
183B (hex) 01F4 (hex)
I/O memory
PCU
CPU Unit
25 words:
Axis 2
25 words:
Axis 1
25 words:
Axis 2
25 words:
Axis 1
: CIO Area
: CIO 100
Function as Axis Operating Output Memory
Areas
CIO 100 to CIO 124: Axis 1
CIO 125 to CIO 149: Axis 2
etc.
Axis Operating Input Memory Area setting
Common Parameters
Axis Operating Output Memory Area setting
: CIO Area
: CIO 500
Function as Axis Operating Input Memory
Areas
CIO 500 to CIO 524CH: Axis 1
CIO 525 to CIO 549CH: Axis 2
etc.
Unit address
Name
Enable timing
183C hex to
1843 hex
Scan list
At powerup or
restart.
Data con-
figuration
15
08 07
00
Data setting range
Default
183C hex
00 or 40
0000
183D hex
00 or 40
0000
183E hex
00 or 40
0000
183F hex
00 or 40
0000
1840 hex
00 or 40
0000
1841 hex
00 or 40
0000
1842 hex
00 or 40
0000
1843 hex
00 or 40
0000
Axis 2 allocation
Axis 1 allocation
Axis 4 allocation
Axis 3 allocation
Axis 6 allocation
Axis 5 allocation
Axis 8 allocation
Axis 7 allocation
Axis 10 allocation
Axis 9 allocation
Axis 12 allocation
Axis 11 allocation
Axis 14 allocation
Axis 13 allocation
Axis 16 allocation
Axis 15 allocation
Содержание CJ1W-NC271 - 12-2009
Страница 2: ......
Страница 4: ...iv ...
Страница 6: ...vi ...
Страница 22: ...xxii ...
Страница 58: ...30 Starting Operation Section 2 2 ...
Страница 244: ...216 Axis Operating Input Memory Areas Section 4 8 ...
Страница 264: ...236 Transferring Servo Parameters Section 5 3 ...
Страница 396: ...368 Linear Interpolation Section 9 7 ...
Страница 648: ...620 List of Error Codes Appendix D ...
Страница 674: ...646 Additional Functions for the CJ1W NCF71 MA Appendix F ...
Страница 684: ...656 Index ...
Страница 686: ...658 Revision History ...