• The engine is ready for operation
•
Engine stops, if
• The reply GCB is open AND the LogicsManager "86.09 LM: Start req.in AUTO" is not
•
fulfilled (FALSE) OR
• A shut down alarm occurs
•
Being parallel to mains or to other generator, the generator power will be reduced before.
╚═▷ “4.4.5.2 Operation Mode AUTO - Automatic Run”
for details.
6.1.2
Application mode A02 (GCB open)
This application mode (
A02
) may be used for islanded operation applications.
In this case, the easYgen will function as an engine control with generator and engine
protection. The control unit can only open the GCB. Emergency mode (AMF operation) is
not supported in this application mode.
682
easYgen-3000XT Series
B37574
6 Application Field
6.1.2 Application mode A02 (GCB open)
Released