ID
Parameter
CL
Setting range
[Default]
Description
Stop by a class 'E' or 'F' alarm
If the engine is stopped by an
alarm of this alarm class, the
engine is shutdown without a cool
down immediately.
Notes
If a critical operation mode (
) is
initiated, the time configured in
critical mode postrun
(parameter 4109) will be used
instead of the cool down time.
3319
Cool down in STOP
mode
2
[Yes]
A cool down will be performed if
the genset is changed to STOP
operation mode.
No
No cool down will be performed if
the genset is changed to STOP
operation mode.
3322
Cool down without
breaker
2
This parameter may be used to
perform a cool down if the
application mode (parameter
) is configured to "None" or
"GCB open".
Yes
A cool down will be performed if a
start signal is disabled or a stop
signal is enabled.
[No]
No cool down will be performed if
a start signal is disabled or a stop
signal is enabled.
Notes
This parameter only applies to
application mode
A01
A02
.
3300
Auxiliary services
prerun
(Prerun auxiliary
operation (start
preparation))
2
0 to 9999 s
[0 s]
Prior to a start sequence being
initiated, the discrete output for
the auxiliary services prerun
(LogicsManager 03.30) remains
enabled for the configured
amount of time to permit engine
related operations (i.e. open
louvers) to be performed.
While this discrete output is
enabled the control screen will
display the message
"Aux.serv.prerun" for the
configured time.
The auxiliary services discrete
output disables when the
operation mode is changed from
the MANUAL operation mode or, if
engine speed is no longer
detected, when the discrete
output for the auxiliary services
postrun (LogicsManager 03.31) is
disabled.
CAUTION
221
easYgen-3000XT Series
B37574
4 Configuration
4.4.1.2 Engine Start/Stop
Released