ID
Parameter
CL
Setting range
[Default]
Description
Closed Transit.
Interchange
[Parallel]
Notes
This parameter only applies to
application mode
A04
.
For a detailed explanation for
each mode refer to
Transition Modes (Breaker Logic)”
12932
Transition mode 2
2
Determined by LogicsManager
86.94
[(0 & 1) & 1]
= 11923
Once the conditions of the
LogicsManager have been fulfilled,
the transition mode configured in
parameter
instead of the standard transition
mode configured in parameter
Notes
This parameter only applies to
application mode
A04
.
Alternative transition mode 1 has
priority over alternative transition
mode 2, i.e. if both LogicsManager
functions (parameters
) are TRUE, breaker
transition mode 1 (parameter
) will be used.
For information on the
LogicsManager and its default
settings see
.
3400
Transfer time GCB<-
>MCB
2
1.00 to 99.99 s
[1.00 s]
Switching from generator supply
to mains supply or from mains
supply to generator supply occurs
automatically if the operating
conditions have been met.
The time between the reply
"power circuit breaker is open"
and a close pulse is set by this
parameter. This time applies for
both directions. During this time
the consumers are de-energized.
Notes
This parameter only applies to
application mode
A04
.
This is only valid, if parameter
is configured to OPEN
TRANSITION
276
easYgen-3000XT Series
B37574
4 Configuration
4.4.3.2 General Breaker Settings
Released