ID
Parameter
CL
Setting range
[Default]
Description
Only the screens and functions
that pertain to the application
mode selected are displayed. The
single line diagram in the main
screen will change.
for additional
information.
None
Application mode
A01
The control unit will function as an
engine start/stop control with
generator and engine protection.
All necessary inputs and outputs
are assigned and pre-defined.
GCB open
Application mode
A02
The control unit will function as an
engine start/stop control with
generator and engine protection.
The control unit can only open the
GCB. All necessary inputs and
outputs are assigned and pre-
defined.
GCB
Application mode
A03
The control unit will function as a
one-CB unit. The control unit
performs full control like
synchronizing, opening and
closing the GCB with generator
and engine protection. All
necessary inputs and outputs are
assigned and pre-defined.
[GCB/MCB]
Application mode
A04
The control unit will function as a
two-CB unit. The control unit
performs full control like
synchronizing, opening and
closing the GCB and the MCB with
generator and engine protection.
The GCB/MCB perform also full
load transfer via open/closed
transition, interchange and
parallel mode. All necessary
inputs and outputs are assigned
and pre-defined.
3411
Breaker transition
mode
2
The control unit automatically
controls the two breakers (MCB
and GCB).
External
Open Transition
Closed Transit.
Interchange
[Parallel]
Notes
274
easYgen-3000XT Series
B37574
4 Configuration
4.4.3.2 General Breaker Settings
Released