• »Communication« for visualizing communication state:
•
◦ Off: no data received by any CAN port
◦
◦ Toggling green/off: any data is received by any CAN port
◦
◦ Red: missing member alarm is active
◦
◦ Toggling red/green: missing member is active and data received by any CAN
◦
port
• »Operation« for device state indication:
•
◦ Off: the unit is not ready for operation (depending on LogicsManager "Ready for
◦
operation)
◦ Green: the unit is ready for operation and no alarm is active or latched
◦
◦ Toggling green/red: the unit is ready for operation and a warning alarm in the
◦
system is active or latched
◦ Red: the unit is ready for operation and a shutdown alarm in the system is
◦
active or latched.
◦ Green blinking fast (about 6 times per second) and red is permanently off:
◦
Internal copy process after flashing a software update is still running or "Load
default settings" is initiated
2.2
Application Modes Overview
The genset control provides the following basic functions via the application modes listed
below.
For detailed information on the application modes and special applications refer to
.
Application
mode
Symbol
Function
None
A01
No breaker control.
This application mode provides the following functions:
• Measuring of engine/generator parameters (i.e. voltage, frequency, current,
•
power, coolant temperature, oil pressure, etc.)
• Engine start/stop
•
GCB open
A02
GCB control (open)
This application mode provides the following functions:
• Measuring of engine/generator parameters (i.e. voltage, frequency, current,
•
power, coolant temperature, oil pressure, etc.)
• Engine start/stop
•
• Engine/generator protection (relay output to open GCB)
•
• Mains failure detection with mains decoupling (GCB)
•
GCB
A03
GCB control (open/close)
54
easYgen-3000XT Series
B37574
2 System Overview
2.2 Application Modes Overview
Released