ID
Parameter
CL
Setting range
[Default]
Description
1146
If the offset feature is utilized, the
value configured in this parameter
will be added to/subtracted from
the measured resistive value.
This has the following effect to the
measured values (please note
tables in
Notes
This parameter is only visible if
the parameter "Sender type" (
) is
configured to "0 to 2000 Ohms".
VDO temperature and pressure
senders use the ± range in
different ways! Please take care
for sender documentation.
1035
1085
1135
Exponent for protocol
2
-2 to 3
[0]
This is the exponent to adapt the
decimal place of the actual value
(parameter 1033/1083/1133) for
the protocol format.
Example
Exponent is 3:
value of analog input {½/3} x 10
3
= value of analog input {½/3} x
1000
1033
Analog input 1
(displayed only)
Current scaled value of the AI {X}
1003
1053
1103
Monitoring wire
break
2
The respective analog input can
be monitored for wire breaks.
If this protective function is
triggered, the display indicates
"Wb: {Text of Parameter
[Description]}" (parameter
).
The following configurations are
used to monitor for wire breaks:
[Off]
No wire break monitoring is
performed.
High
If the actual value rises over the
maximum value (overshoot), this
is identified as a wire break.
Low
If the actual value falls below the
minimum value (undershoot), this
is identified as a wire break.
High/Low
If the actual value rises over the
maximum value (overshoot) or
falls below the minimum value
(undershoot), this is identified as a
wire break.
Notes
Monitoring of the analog inputs
(overrun/underrun) must be
247
easYgen-3000XT Series
B37574
4 Configuration
4.4.2.4.2 Analog Inputs 1 to 3 (0 to 2000 Ω | 0/4 to 20 m A | 0 to 1 V)