96.01 LM: Flag 1, 96.02 LM: Flag
2, ..., 96.32 LM: Flag 32
4.5.3.14 Mains Import Power (Level 1 & 2)
General notes
It is possible to monitor two independently configurable mains import power limit values.
This function makes it possible to initiate external load shedding.
If this protective function is triggered, the display indicates "Mains import power 1" or
"Mains import power 2" and the logical command variable "07.21" or "07.22" will be
enabled.
ID
Parameter
CL
Setting range
[Default]
Description
3200
3206
Monitoring
2
On
Mains import power monitoring is
carried out according to the
following parameters. Monitoring
is performed at two levels. Both
values may be configured
independent from each
other (prerequisite: Level 1 limit
< Level 2 limit).
[Off]
Monitoring is disabled for Level 1
limit and/or Level 2 limit.
3215
3216
Monitoring at
2
[Overrun]
The monitored value must exceed
the limit to be considered as out
of limits.
Underrun
The monitored value must fall
below the limit to be considered
as out of limits.
3204
3210
Limit
2
0.00 to +150.00%
3204: [80.00%]
3210: [100.00%]
If this threshold value has been
exceeded or fallen below
(depending on the setting of
parameter
for at least the delay time
(parameter
), the action specified by the
alarm class is initiated.
Notes
This value refers to the Mains
rated active power (parameter
3213
3214
Hysteresis
2
0.00 to 99.99%
[0.01%]
(Reset Delay: 80 ms)
The monitored mains power level
must return within the limits
configured in parameter
or
(depending on the setting of
parameter
the value configured here, to reset
the alarm.
530
easYgen-3000XT Series
B37574
4 Configuration