Fig. 308:
LogicsManager command chain words 2 and 3
Words 2 and 3 contain a sequence of nibbles each representing a sign or operator of the
equation.
The Data words table below shows the sequence how to arrange the LogicsManager
setting that build the command chain.
Word 2
Word 3
Sign 1
Operator 1
Sign 2
Operator 2
Sign 3
not used
not used
not used
Table 118: Data words 2 and 3 - details of the logic equations
Please find the hex code equivalents on the table below:
Signs
Operators
"NOT"
0
"AND"
0
"—"
1
"NAND"
1
"TRUE"
2
"OR"
2
"FALSE"
3
"NOR"
3
"XOR"
4
"NOT-XOR"
5
Table 119: Hex code equivalents of the logic equations' nibbles
The hex code of words 2 and 3 is taken "as is" ¾ don't swap high byte and low byte.
805
easYgen-3000XT Series
B37574
6 Application Field
6.5.2.2 Configuration Of LogicsManager Functions
Released