ID
Parameter
CL
Setting range
[Default]
Description
parameter has priority over
parameters
[(0 & 1) & 1]
Notes
For information on the
LogicsManager and its default
settings see
.
12928
Segment no.3 act.
2
Determined by LogicsManager
86.88
Once the conditions of the
LogicsManager have been fulfilled,
this genset is assigned load share
segment number 3 (this
parameter has priority over
parameters
[(0 & 1) & 1]
Notes
For information on the
LogicsManager and its default
settings see
.
12927
Segment no.4 act.
2
Determined by LogicsManager
86.89
Once the conditions of the
LogicsManager have been fulfilled,
this genset is assigned load share
segment number 4.
[(0 & 1) & 1]
Notes
For information on the
LogicsManager and its default
settings see
.
5568
Mode ext. load share
gateway
2
The operation mode for the
external Woodward Load Share
Gateway (LSG) is configured here.
[0]
Off
1
Woodward EGCP-2
RS-485 (P & Q)
2
Woodward SPM-D
R = 4.99k | P: 0 − 4 V (0 to 100%)
| Q: 0 − 5 V (-85% to +85%)
Woodward MFR 15
R = 4.99k | P: 0 − 4 V (0 to 100%)
3
Woodward 2301 A
R = 54.90k | P: 0 − 3 V (0 to
100%)
4
Caterpillar LSM
R = 25.00k | P: 0 − 3 V (0 to
100%)
5
Cummins PCC 3100, 3200, 3201,
3300
337
easYgen-3000XT Series
B37574
4 Configuration
4.4.4.3.8 Load Share Control Grouping
Released