ID
Parameter
CL
Setting range
[Default]
Description
For more information about dead
busbar closure/negotiation, see
╚═▷ “4.4.3.1 Good to know:
Actions with Breakers”
3472
Dead bus closure
multi segment
2
[On]
A dead busbar negotiation is done
over all segments in the system.
Off
A dead busbar negotiation is done
only in the own segment.
Notes
This parameter only applies to
application modes
A03
and
A04
.
For more information about dead
busbar closure/negotiation, see
╚═▷ “4.4.3.1 Good to know:
Actions with Breakers”
15161
Inh.dead bus GCB
2
Determined by LogicsManager
87.74
[(0 & 1) & 1]
= 11463
If active the dead bus closure of
the GCB can be inhibited.
Notes
For information on the
LogicsManager and its default
settings see
.
3415
Generator stable
time
2
0 to 99 s
[2 s]
The time configured here begins
to count down once the »Engine
monitoring delay timer«
has expired. This permits for an
additional delay time before the
breaker is closed in order to
ensure that none of the engine
delayed watchdogs trips.
It is possible to bypass this delay
time through the LogicsManager
(parameter
) in the
event an emergency operation
condition (mains failure) occurs.
Unnecessary CB switching
operations and voltage
interruptions should be avoided by
utilizing this parameter.
Notes
This parameter only applies to
application mode
A02
A03
A04
.
After »Generator stable time« has
expired, then "03.08 Break. delay
expired" becomes TRUE.
12210
Undelay close GCB
2
Determined by LogicsManager
86.12
[(04.09 Emergency mode & 1)
& 1]
= 10711
Once the conditions of the
LogicsManager have been fulfilled
the GCB will be closed
immediately (without waiting for
engine speed delay and generator
stable timer to expire).
When using the standard setting,
the GCB will be closed without
282
easYgen-3000XT Series
B37574
4 Configuration
4.4.3.3 Configure Breakers: GCB
Released