ID
Parameter
CL
Setting range
[Default]
Description
determined through the
LogicsManager equation "Release
engine monitoring".
For xx = 1 to 32:
96.{xx}
LM: Flag{xx}
The monitoring is executed, if the
LogicsManager "Flag {xx}" is
TRUE.
Example:
96.01 LM: Flag 1, 96.02 LM: Flag
2, ..., 96.32 LM: Flag 32
Table 75: J1939 Monitoring: Device 1
Device 2 settings
ID
Parameter
CL
Setting range
[Default]
Description
15183
Monitoring
2
On
Monitoring of the CAN messages
of device 2 is carried out
according to the following
parameters.
[Off]
Monitoring is disabled.
15184
Address
2
0-255
[1]
This device address is monitored.
15188
Delay
2
0.02 to 999.00 s
[1.00 s]
The delay is configured with this
parameter. If the interface does
not receive a CAN message from
device 2 within this delay time,
the action specified by the alarm
class is initiated.
The delay timer is re-initialized if
any message from the device 2 is
received.
15185
Alarm class
2
Class A, Class B, Class C, Class D,
Class E, Class F , Control
[Class B]
Each limit may be assigned to an
independent alarm class that
specifies what action should be
taken when the limit is surpassed.
Notes
For additional information refer to
15186
Self acknowledge
2
[Yes]
The control unit automatically
clears the alarm if the fault
condition is no longer detected.
No
The control unit does not
automatically reset the alarm
when the fault condition is no
longer detected.
The alarm must be acknowledged
and reset by manually pressing
the appropriate buttons or by
activating the LogicsManager
output "External
564
easYgen-3000XT Series
B37574
4 Configuration
4.5.6.6 CAN Interface 2 - J1939 Interface
Released