ID
Parameter
CL
Setting range
[Default]
Description
between minimum and maximum
generator load (parameters
) after the new
genset has been started.
Stopping genset
The genset will shut down at a
lower limit and be operated
longer. The number of gensets in
operation will remain constant for
a wider range of load. The load on
the remaining gensets must not
exceed 25 % of the range
between minimum and maximum
generator load (parameters
).
Moderate
Starting genset
A medium genset is requested.
The requested load is calaculated
so that the gensets will be loaded
with 50 % of the range between
minimum and maximum
generator load (parameters
) after the new
genset has been started.
Stopping genset
The load on the remaining gensets
must not exceed 50 % of the
range between minimum and
maximum generator load
(parameters
).
Strong
Starting genset
A smaller genset is requested to
operate the engines with higher
efficiency. This may lead to more
frequent starts and stops. The
requested load is calaculated so
that the gensets will be loaded
with 75 % of the range between
minimum and maximum
generator load (parameters
) after the new
genset has been started.
Stopping genset
The genset will be shut down
earlier. This may lead to more
frequent starts and stops. The
load on the remaining gensets
must not exceed 75 % of the
range between minimum and
maximum generator load
(parameters
).
Notes
This parameter is only effective if
start stop mode (parameter
407
easYgen-3000XT Series
B37574
4 Configuration
4.4.5.5.4 Islanded Parallel Operation (IOP)
Released