Cold, Dry Heat (operating)
-20 °C (-4 °F) / 70 °C (158
°F)
-40 °C (-40 °F) / 70 °C (158
°F)
Sheet metal
Cold, Dry Heat (storage)
-40 °C (-40 °F) / 80 °C (176 °F)
Cold, Dry Heat (operating)
-40 °C (-40 °F) / 70 °C (158 °F)
Standards
IEC 60068-2-2, Test Bb and Bd
IEC 60068-2-1, Test Ab and Ad
Humidity
Humidity
60 °C, 95% RH, 5 days
Standards
IEC 60068-2-30, Test Db
Marine environmental categories
Marine environmental categories
Lloyd’s Register of Shipping (LRS):
ENV1, ENV2, ENV3 and ENV4
Electromagnetic Compatibility
EN 61000-6-2
2005 - Electromagnetic compatibility (EMC). Generic
standards.
Immunity for industrial environment
EN 61000-6-4
2007 + A1: 2011 - Electromagnetic compatibility
(EMC). Generic standards.
Emission standard for industrial environments
EN 61326-1
2013 - Electrical equipment for measurement,
control and laboratory use.
EMC requirements. General requirements (according
to industrial electromagnetic environment)
8.3
Accuracy
The accuracy declaration is defined by the according measurement ranges. The rated
maximum of the single ranges are taken as 100%.
This results in the definitions:
• Range 1: 69/120 V rated = 100%
•
• Range 2: 277/480 V rated = 100%
•
•
Measuring value
Display
Accuracy
Measuring start
Notes
Frequency
Generator
15.0 to 85.0 Hz
0.1% (of 85 Hz)
5% (of PT secondary
voltage setting)
1
Mains
30.0 to 85.0 Hz
858
easYgen-3000XT Series
B37574
8 Technical Specifications
8.3 Accuracy
Released