
Weighting %
LS Gain
30
1.75
40
1.5
50
1.25
60
1
70
0.75
80
0.5
90
0.25
98
0.05
4.4.4.3.8
Load Share Control Grouping
Load sharing with several gensets is possible for a supply of several split busbars. Each of
this individual groups is called a segment.
Up to four segments can be managed easily for load share by LogicsManager!
General
A group breaker splits the busbar in a way that some gensets supply one busbar and
some supply another one. However, it is necessary to group the gensets, which supply
the same busbar.
The designer of a busbar system gives all individual bus bars an own number: The
Segment Number for the easYgen is defined with ID 1723. Each easYgen is connected
with its GCB on one of these segments.
The configured segment number can be changed to one of three alternative segment
numbers by three LogicsManager equations. These LogicsManager equations stand for
the segment numbers 2, 3, or 4. They are usually controlled by circuit breaker reply
auxiliary contacts. This is finally the segment number the easYgens interacts with.
335
easYgen-3000XT Series
B37574
4 Configuration
4.4.4.3.8 Load Share Control Grouping
Released