ID
Parameter
CL
Setting range
[Default]
Description
Notes
This value is rated to the absolute
difference between generator
rated power (parameter
) and the percent average
power of the other devices. The
generator rated power is modified
by the derating factor if derating
is activated.
5104
Delay
2
1.0 to 999.9 s
[10.0 s]
If the monitored generator power
value exceeds the threshold value
for the delay time configured
here, an alarm will be issued.
Notes
If the monitored generator power
falls below the threshold (minus
the hysteresis) before the delay
expires the time will be reset.
5101
Alarm class
2
Class A, Class B, Class C, Class D,
Class E, Class F , Control
[Class B]
Each limit may be assigned an
independent alarm class that
specifies what action should be
taken when the limit is surpassed.
Notes
For additional information refer to
5102
Self acknowledge
2
Yes
The control unit automatically
clears the alarm if the fault
condition is no longer detected.
[No]
The control unit does not
automatically reset the alarm
when the fault condition is no
longer detected.
The alarm must be acknowledged
and reset by manually pressing
the appropriate buttons or by
activating the LogicsManager
output "External
acknowledgment" (via a discrete
input or via an interface).
5103
Enabled
2
[Always]
Monitoring for this fault condition
is continuously enabled.
87.70 LM:Eng.mon
Monitoring for fault conditions is
not performed until engine
monitoring is enabled. This is
determined through the
LogicsManager equation "Release
engine monitoring".
For xx = 1 to 32:
96.{xx}
LM: Flag{xx}
The monitoring is executed, if the
LogicsManager "Flag {xx}" is
TRUE.
Example:
96.01 LM: Flag 1, 96.02 LM: Flag
2, ..., 96.32 LM: Flag 32