CAN load share configuration
The following parameters are available for configuring the CAN bus interfaces. Refer to
╚═▷ “4.7.4.3 CAN Load Share Parameters”
for detailed information.
Open menu path [Parameter / Configuration / Configure interfaces / Configure CAN
interfaces / Configure CAN load share]. Refer to
.
ID
Text
Setting range
Default value
9921
Transfer rate LS fast message
0.10 to 0.30 s
0.10 s
9999
Load share timeout factor
2 to 20
2
9920
Load share CAN-ID
2xx Hex / 3xx Hex /
4xx Hex / 5xx Hex
5xx Hex
7.7.2
Load Share via UDP Broadcast Messages (Ethernet)
Load Share UDP
Load share and other system relevant messages are handled with UDP messages. The
construction of the UDP messages allows (load share) communication with other
Woodward devices.
For configuration of the Ethernet interface see chapters
╚═▷ “4.7.5 Ethernet Interfaces”
and
849
easYgen-3000XT Series
B37574
7 Interfaces And Protocols
7.7.2 Load Share via UDP Broadcast Messages (Ethernet)
Released