ID
Parameter
CL
Setting range
[Default]
Description
operating limits (
Generator Operating Ranges:
Voltage / Frequency / Busbar”
5500
Int. freq. control
setpoint 1
(Internal frequency
control setpoint 1)
2
15.00 to 85.00 Hz
[50.00 Hz]
The internal generator frequency
setpoint 1 is defined in this
screen.
This value is the reference for the
frequency controller when
performing islanded and/or no-
load operations.
Generally 50 Hz or 60 Hz will be
the values entered into this
parameter. It is possible to enter a
different value here.
5519
AM Frequency
SP2[Hz]
2
Determined by AnalogManager
81.04
[A1 = 05.52 Internal f setp2
[Hz]]
The Frequency setpoint 2 source
may be selected from the
available data sources.
The internal frequency setpoint
05.52 can be changed manually at
the setpoint screen of the display.
Notes
The frequency setpoint may be
adjusted within the configured
operating limits (
Generator Operating Ranges:
Voltage / Frequency / Busbar”
5501
Int. freq. control
setpoint 2
(Internal frequency
control setpoint 2)
2
15.00 to 85.00 Hz
[50.00 Hz]
The internal generator frequency
setpoint 2 is defined in this
screen.
This value is the reference for the
frequency controller when
performing islanded and/or no-
load operations.
Generally 50 Hz or 60 Hz will be
the values entered into this
parameter. It is possible to enter a
different value here.
5502
Slip frequency
setpoint offset
2
0.00 to 0.50 Hz
[0.10 Hz]
This value is the offset for the
synchronization to the busbar/
utility.
With this offset, the unit
synchronizes with a positive slip.
Example
If this parameter is configured to
0.10 Hz and the busbar/mains
frequency is 50.00 Hz, the
synchronization setpoint is
50.10 Hz.
Notes
347
easYgen-3000XT Series
B37574
4 Configuration
4.4.4.4 Frequency Control