HMI Text
Note
03.54 Wait to start lamp
TRUE if ECU Engine Wait to Start Lamp: on (SPN 1081) is active.
(In Deutz EMR mode: Preheat active.)
03.57 DPF:Pass.regeneration
TRUE if ECU Diesel Particulate Filter Passive Regeneration Status: Active (SPN
3699) is active.
03.58 DPF:Act.reg.inhibit
TRUE if ECU Diesel Particulate Filter Active Regeneration Inhibited Status: Inhibited
(SPN 3702) is active.
03.73 Restored oper. active
(03.73 to 03.85 are for Volvo EMS2. Only as command variables available.)
State of 15859 "Restored operation": "Restored operation active"
03.74 Restored oper. error
State of 15859 "Restored operation": "Restored operation error"
03.75 SCR: no inducement
State of 15857 "SCR inducement severity": "No inducement active"
03.76 SCR: warning
State of 15857 "SCR inducement severity": "Inducement warning"
03.77 SCR: derate active
State of 15857 "SCR inducement severity": "Derate active"
03.78 SCR: derate! warning
State of 15857 "SCR inducement severity": "Pre severate derate warning"
03.79 SCR: severe derate!
State of 15857 "SCR inducement severity": "Severe derate"
03.80 SCR: override derate
State of 15857 "SCR inducement severity": "Temporary override of derate"
03.81 SCR: OK
State of 15858 "SCR inducement reason": "OK"
03.82 SCR: Tank level low
State of 15858 "SCR inducement reason": "Reagent tank low level"
03.83 SCR: Reagent quality
State of 15858 "SCR inducement reason": "Incorrect reagent quality"
03.84 SCR: Absence dosing
State of 15858 "SCR inducement reason": "Absence of reagent dosing"
03.85 SCR: Tampering
State of 15858 "SCR inducement reason": "Tampering"
03.86 DPF1 Act.reg.inhibit
"Active DPF regeneration inhibited" (SPN 3750 DPF1 Conditions Not Met for Active
Regeneration.)
03.87 Inhibit Switch
(SPN 3703 DPF regeneration inhibited due to Inhibit Switch.)
03.88 Low exhaust temp.
(SPN 3711 DPF regeneration inhibited due to Low Exhaust Gas Temperature.)
03.89 System fault active
Inhibited Switch (SPN 3712 DPF regeneration inhibited due to System fault.)
03.90 System timeout
Inhibited Switch (SPN 3713 DPF regeneration inhibited due to System Timeout.)
03.91 Temporary lockout
Inhibited Switch (SPN 3714 DPF regeneration inhibited due to Temporary System
Lockout.)
03.92 Permananent lockout
Inhibited Switch (SPN 3715 DPF regeneration inhibited due to Permanent System
Lockout.)
03.93 Engine not warmed up
Inhibited Switch (SPN 3716 DPF regeneration inhibited due to Engine Not Warmed
Up.)
03.94 Low exhaust pressure
Inhibited Switch (SPN 5466 DPF regeneration inhibited due to Low Exhaust Gas
Pressure.)
9.3.2.4
Group 04: Application conditions
HMI Text
Note
04.01 Operat. mode AUTO
TRUE if operating mode AUTOMATIC is active.
04.02 Operat. mode STOP
TRUE if operating mode STOP is active.
04.03 Operat. mode MAN
TRUE if operating mode MANUAL is active.
1089
easYgen-3000XT Series
B37574
9 Appendix
9.3.2.4 Group 04: Application conditions
Released