ID
Parameter
CL
Setting range
[Default]
Description
If the ECU sends the Red Stop
Lamp On message, the action
specified by the alarm class is
initiated after the delay configured
here expires.
15116
Alarm class
2
Class A, Class B, Class C, Class D,
Class E, Class F , Control
[Class A]
Each limit may be assigned an
independent alarm class that
specifies what action should be
taken when the limit is surpassed.
Notes
For additional information refer to
15117
Self acknowledge
2
[Yes]
The control unit automatically
clears the alarm if the fault
condition is no longer detected.
No
The control unit does not
automatically reset the alarm
when the fault condition is no
longer detected.
The alarm must be acknowledged
and reset by manually pressing
the appropriate buttons or by
activating the LogicsManager
output "External
acknowledgment" (via a discrete
input or via an interface).
15118
Enabled
2
[Always]
Monitoring for this fault condition
is continuously enabled.
87.70 LM:Eng.mon
Monitoring for fault conditions is
not performed until engine
monitoring is enabled. This is
determined through the
LogicsManager equation "Release
engine monitoring".
For xx = 1 to 32:
96.{xx}
LM: Flag{xx}
The monitoring is executed, if the
LogicsManager "Flag {xx}" is
TRUE.
Example:
96.01 LM: Flag 1, 96.02 LM: Flag
2, ..., 96.32 LM: Flag 32
4.5.6.8
J1939 Interface - Amber Warning Alarm
General notes
This monitor monitors, whether a specific alarm bit is received from the CAN J1939
interface. This enables to configure the easYgen in a way that a reaction is caused by this
bit (e.g. warning, shutdown).
567
easYgen-3000XT Series
B37574
4 Configuration
4.5.6.8 J1939 Interface - Amber Warning Alarm