ID
Parameter
CL
Setting range
[Default]
Description
from the configured load setpoint
by more than the value configured
in this parameter without the
controller issuing a raise/lower
signal to the speed control.
This prevents unneeded wear on
the raise/lower relay contacts. The
configured percentage for the
dead band refers to the generator
rated active power
(parameter
Notes
This parameter is only visible if
load control (parameter
)
is configured to "3pos controller".
5561
Time pulse minimum
1
0.01 to 2.00 s
[0.05 s]
A minimum pulse on time must be
configured here.
The shortest possible pulse time
should be configured to limit
overshoot of the desired speed
reference point.
Notes
This parameter is only visible if
load control (parameter
)
is configured to "3pos controller".
5562
Gain factor
1
0.1 to 10.0
[5.0]
The gain factor K
p
influences the
operating time of the relays.
By increasing the number
configured in this parameter, the
operating time of the relay will be
in-creased in response to a
deviation from the frequency
reference.
By increasing the gain, the
response is increased to permit
larger corrections to the variable
to be controlled. The farther out of
tolerance the process is the larger
the response action is to return
the process to the tolerance band.
Notes
If the gain is configured too high,
the result is excessive overshoot/
undershoot of the desired value.
This parameter is only visible if
load control (parameter
)
is configured to "3pos controller".
5637
Cycle time factor
1
1.0 to 20.0
[1.0]
The cycle time factor adjusts the
time between the pulses (pause
time).
By increasing the cycle time
factor, the time between the
pulses increases.
353
easYgen-3000XT Series
B37574
4 Configuration
4.4.4.5.1 Configure: Load Control (general)
Released