ID
Parameter
CL
Setting range
[Default]
Description
5210
5224
PWM output level
2
0.00 to 10.00 V
[10.00 V]
If PWM has been enabled in
parameter
defined in %, and the level of the
PWM signal (amplitude) may be
adjusted here.
5204
5218
Source value at
minimum level
2
-21000000.00 to 21000000.00
[0.00]
The value from the data source
must exceed the value configured
here to raise the output signal
above minimum hardware level.
Negative values may be used to
change the sign e.g. for power.
The entry format of the value
depends on the selected data
source.
5206
5220
Source value at
maximum level
2
-21000000.00 to 21000000.00
[100.00]
If the value from the data source
reaches the value configured here,
the output signal will reach
maximum hardware level.
Negative values may be used to
change the sign e.g. for power.
The entry format of the value
depends on the selected data
source.
5203
5217
Filter time constant
CL05
2
Off, 1 to 7
A filter time constant may be used
to reduce the fluctuation of an
analog output value.
[Off]
The analog output is displayed
without filtering.
1
Cut-off-frequency = 3.98 Hz (filter
time constant = 0.04 s)
2
Cut-off-frequency = 1.98 Hz (filter
time constant = 0.08 s)
3
Cut-off-frequency = 0.99 Hz (filter
time constant = 0.16 s)
4
Cut-off-frequency = 0.5 Hz (filter
time constant = 0.32 s)
5
Cut-off-frequency = 0.25 Hz (filter
time constant = 0.64 s)
6
Cut-off-frequency = 0.12 Hz (filter
time constant = 1.28 s)
7
Cut-off-frequency = 0.06 Hz (filter
time constant = 2.56 s)
Notes
The filter is not applied to the
analog output display value, i.e.
the end value of the analog output
is displayed immediately.
254
easYgen-3000XT Series
B37574
4 Configuration
4.4.2.5.1 Analog Outputs 1 and 2
Released