Schematic and terminals
A
B
Relay output
max. 250 Vac/dc
2A
N /
External Device
Fig. 68:
Relay outputs - schematic
Terminal
Description
N.O.
Common
A
B
Form A
42
41
Relay output [R 01]
All
Fixed to "Ready for operation"
1
43
46
Relay output [R 02]
All
Preconfigured to "Centralized alarm"
1
44
Relay output [R 03]
All
Preconfigured to "Starter"
1
45
Relay output [R 04]
All
Preconfigured to "Fuel solenoid / gas valve"
1
48
47
Relay output [R 05]
All
Preconfigured to "Preglow"
1
50
49
Relay output [R 06]
A01
LogicsManager
1
A02
A03
Preconfigured to "Command: close GCB"
1
A04
52
51
Relay output [R 07]
A01
Preconfigured to "Mains decoupling"
1
A02
Preconfigured to "Command: open GCB"
1
A03
A04
54
53
Relay output [R 08]
A01
LogicsManager
1
A02
A03
A04
Preconfigured to "Command: close MCB"
1
56
55
Relay output [R 09]
A01
Preconfigured to "Mains decoupling"
1
A02
A03
A04
Preconfigured to "Command: open MCB"
1
57
60
Relay output [R 10]
All
Preconfigured to "Auxiliary services"
1
58
Relay output [R 11]
All
Preconfigured to "Alarm class A and B"
1
59
Relay output [R 12]
All
Preconfigured to "Alarm class C, D, E or F"
1
103
easYgen-3000XT Series
B37574
3 Installation
3.3.11 Relay Outputs (LogicsManager)
Released