communication interface (usually CANbus). This allows determining, if the Single-Failure-
Proof is lost and the unit can issue an alarm.
Using Ethernet?
To us Ethernet communication interface for Single-failure-proof it is mandatory that load-
share is using Ethernet, too. For interface selection refer to
Enable 4105 monitoring
Monitoring according VDE AR-N 4105 per default is [Off]. It can be enabled via ToolKit
[Configure monitoring / Mains / Other monitoring / Setup VDE-AR-N 4105] or via Menu
(see screen
).
Fig. 193:
Select mains decoupling 4105
Monitoring according AR-–4105
ID
Parameter
CL
Setting range
[Default]
Description
3297
Monitoring
2
[Off]
The diagnostic function is
disabled, no related monitoring is
executed.
CAN #1, Ethernet
If the diagnostic function is
enabled, the related messages
495
easYgen-3000XT Series
B37574
4 Configuration
4.5.3.4.1 Setup Grid Code AR-–4105