ID
Parameter
CL
Setting range
[Default]
Description
5200
5214
AM Data source AO1
2
Determined by AnalogManager
93.01, 93.02
AO1: [A1 = 11.03 Speed bias
[%]
AO2: [A1 = 11.02 Voltage bias
[%]
The data source may be selected
from the available data sources.
Notes
for a list of all data sources.
5201
5215
Selected hardware
type
2
This parameter is used to
configure the appropriate type of
analog controller signal. The range
of the analog output is configured
here.
PMW value is defined in %.
Off
No analog output signal will be
issued.
[mA]
Notes
Because of different isolation
purposes the two biasing outputs
must be clear labeled with their
function.
V
PWM
5208
5222
Minimum hardware
level
(User defined minimum
output value)
2
-20.00 to 100.00
[0.00]
The value of the configured
hardware range, which shall
correspond with the configured
minimum source value, must be
entered here (y-axis). This
specifies the minimum limit of the
hardware range.
Example
If the value configured here is 2.5,
the maximum output range of
“+/-20 mA” / “+/-10 V” has a
lower limit of 2.5 mA / 2.5 V.
Notes
Value »100« is possible only for
PWM.
5209
5223
Maximum hardware
level
(User defined maximum
output value)
2
-20.00 to 100.00
[20.00]
The value of the configured
hardware range, which shall
correspond with the configured
maximum source value, must be
entered here (y-axis). This
specifies the maximum limit of the
hardware range.
Example
If the value configured here is 7.5,
the maximum output range of
“+/-20 mA” / “+/-10 V” has a
upper limit of 7.5 mA / 7.5 V.
Notes
Value »100« is possible only for
PWM.
253
easYgen-3000XT Series
B37574
4 Configuration
4.4.2.5.1 Analog Outputs 1 and 2