ID
Parameter
CL
Setting range
[Default]
Description
3026
3031
Self acknowledge
2
4
Yes
The control unit automatically
clears the alarm if the fault
condition is no longer detected.
[No]
The control unit does not
automatically reset the alarm
when the fault condition is no
longer detected.
The alarm must be acknowledged
and reset by manually pressing
the appropriate buttons or by
activating the LogicsManager
output "External
acknowledgment" (via a discrete
input or via an interface).
3027
3032
Enabled
2
[Always]
Monitoring for this fault condition
is continuously enabled.
87.70 LM:Eng.mon
Monitoring for fault conditions is
not performed until engine
monitoring is enabled. This is
determined through the
LogicsManager equation "Release
engine monitoring".
For xx = 1 to 32:
96.{xx}
LM: Flag{xx}
The monitoring is executed, if the
LogicsManager "Flag {xx}" is
TRUE.
Example:
96.01 LM: Flag 1, 96.02 LM: Flag
2, ..., 96.32 LM: Flag 32
4.5.4
Breaker
4.5.4.1
Configure GCB
General notes
Circuit breaker monitoring contains two alarms: A "breaker reclose" alarm and a "breaker
open" alarm.
"Breaker reclose alarm"
If the control initiates a close of the breaker and the breaker fails to close after the
configured number of attempts the monitoring CB alarm will be initiated (refer to
parameter "GCB maximum closing attempts", parameter
).
If this protective function is triggered, the display indicates "GCB fail to close" and the
logical command variable "08.05" will be enabled.
"Breaker open alarm"
539
easYgen-3000XT Series
B37574
4 Configuration
4.5.4 Breaker
Released