ID
Parameter
CL
Setting range
[Default]
Description
your ECU (xxx.ecu file and
ECU specific settings).
15106
J1939 own
address
2
0 to 255
[234]
The easYgen sends J1939
request and control
messages with this source
address. It must be
changed for different ECU
types according to the
following table. The ECU
listens only to control
messages, if they are sent
to the correct address.
• S6/S8 Scania: 39
•
• EMR2 Deutz: 3
•
• EMS2 Volvo: 17
•
• ADEC ECU7 MTU: 1
•
• EGS Woodward: 234
•
• MFR/EDC7 MAN: 253
•
• EEM SISU: N/A
•
• Cummins: 220
•
• ADEC ECU8/ECU9
•
MTU: 234
• Hatz EDC17: 3
•
• Standard: Please refer
•
to
and to the
manual of your J1939
ECU manufacturer.
Details may be found in the
manual of the genset
control and in
.
15107
Engine control
address
2
0 to 255
[0]
Configures the address of
the J1939 device, which is
controlled. The easYgen
sends J1939 request and
control messages with this
destination address.
• S6/S8 Scania: 0
•
• EMR2 Deutz: 0
•
• EMS2 Volvo: 0
•
• ADEC ECU7 MTU: 128
•
• EGS Woodward: 0
•
• MFR/EDC7 MAN: 39
•
631
easYgen-3000XT Series
B37574
4 Configuration
4.7.4.2.2 J1939 Interface
Released