Remote
control
parameter
Availability with supported ECU number ...
Comment
1
2
3
4
5
6
7
8
9
10
11
12
is present in the easYgen.
The "Stop" bit information
remains set, until ignition
speed is fallen below. After
ignition speed has been
fallen below, the "Stop" bit
will be reset
(LogicsManager command
variable 03.27. "Stop
solenoid").
Droop
mode
Yes
Yes
No
Yes
Yes
Yes
Yes
Yes
Yes
Yes
No
No
This J1939 bit information is
set, if a "Start" command in
automatic or manual mode
is initiated by the easYgen.
The bit remains set until the
engine has been stopped.
Notes
This message is only sent, if
the LogicsManager output
"86.25 LM: Freq. droop act."
is TRUE.
Idle
Mode
No
Yes
No
1
Yes
Yes
No
No
1
No
1
No
Yes
Yes
No
This J1939 bit information is
set, if "Idle" mode is active
(LogicsManager command
variable 04.15. "Idle run
active" is TRUE).
The bit will be reset, if "Idle"
mode is no longer active
(LogicsManager command
variable 04.15. "Idle run
active" is FALSE).
50/60 Hz
switch
Yes
Yes
No
Yes
2
No
Yes
No
1
No
No
Yes
Yes
No
The J1939 information for
50 or 60 Hz mode is sent to
the ECU depending on the
"Rated system frequency"
parameter setting (
Speed
bias
Yes
3
Yes
4
Yes
3
Yes
4
Yes
3
Yes
3
Yes
3
Yes
3
Yes
3
Yes
4
Yes
3
Yes
3
Refer to parameter
information.
Notes
Analog signal only
Preglow
No
No
No
Yes
Yes
No
No
No
No
No
No
No
This J1939 bit information is
set, if the easYgen is in
"Preglow" mode
(LogicsManager command
variable 03.04. "Preglow/
Ignition" is TRUE).
The bit will be reset, if the
"Preglow" phase has been
expired or aborted.
Override
No
Yes
No
Yes
No
Yes
No
Yes
No
Yes
Yes
No
This J1939 bit information is
set, if the easYgen is in
critical mode
(LogicsManager command
variable 04.27. "Critical
mode" is TRUE).
839
easYgen-3000XT Series
B37574
7 Interfaces And Protocols
7.5.2 Supported J1939 ECUs & Remote Control Messages
Released