ID
Parameter
Value
Comment
AnalogManager
81.05
[A1 =
05.54
Internal P
setp1
[kW]]
5526
Load
setpoint 1
Import
The internal power setpoint 1 is a import power value
5520
Int. load
control
setpoint 1
2000.0 kW
The internal power setpoint 1 is configured to 2 MW
5540
AM
ActPower
SP2 [kW]
Pass
through of:
06.03
Analog
input 3
Analog input 3 is used as load setpoint 2
5527
Load
setpoint 2
Steady
The internal power setpoint 1 is a import power value
5521
Int. load
control
setpoint 2
1000.0 kW
The internal power setpoint 1 is configured to 1 MW
12919
12998
12269
Setp. 2
load
Setp. 3
load
Setp. 4
load
FALSE
LogicsManagers are not enabling load setpoint 2, 3, 4
3. ▷
Fig. 222:
LogicsManager function "Setp. 2 load"
Configure the LogicsManager function 12919 "Setp. 2 load" as shown in (
) to
enable load setpoint 2 if discrete input [DI 09] is energized.
4. ▷
Continue similarly with setpoint 3 and setpoint 4
Viewing the load setpoint on the easYgen
⚙
706
easYgen-3000XT Series
B37574
6 Application Field
6.3.2 Configuring A Setpoint Control Via Analog Input
Released