Fig. 162:
Power factor characteristic (schematic)
The characteristic is defined by four points (① .. ④). The power factor corresponding to
this characteristic is available as data source 05.29 in the AnalogManager.
To use this function, the source (05.29) must be applied as source to one of the setpoints
e.g., "Power factor setpoint 1" (parameter
).
ID
Parameter
CL
Setting range
[Default]
Description
5786
Power factor
characteristic
2
[PF(P)]
A power factor setpoint is
determined according to the
characteristic curve: Power factor
in relation to the actual Generator
power.
Q(V)
A power factor setpoint is
calculated according to the
characteristic curve: Generator
reactive power in relation to the
mains voltage.
5787
Point 1 power
2
0.00 to 150.00%
[0.00%]
The value entered into "Point 1
power" defines the cos phi (P)
characteristic.
5788
Point 1 cos phi
2
-0.999 to 1.000
[-0.950]
The desired "Point 1 cos phi" may
be configured here which defines
the cos phi (P) characteristic.
The designations "+" and "-"
stand for inductive/lagging
(generator overexcited) and
312
easYgen-3000XT Series
B37574
4 Configuration
4.4.4.2.3.1 Power factor characteristic PF(P)
Released