Modbus-
Address
CAN
Mux
CAN
Byte
Size
Index
Description
Unit
Scale
Model
04.20 Close command GCB is active
Mask: 0040h
All
04.21 Synchronisation MCB procedure is
active
Mask: 0020h
All
04.22 Open command MCB is active
Mask: 0010h
All
04.23 Close command MCB is active
Mask: 0008h
All
04.28 Unloading generator is active
Mask: 0004h
All
04.29 Unloading mains is active
Mask: 0002h
All
04.30 Power limited prerun
Mask: 0001h
All
50138
46
1-2
uint16 4156
BITLIST
04.16 GGB is closed
Mask: 8000h
EG3500XT-
P1
EG3500XT-
P2
04.17 GGB is released
Mask: 4000h
EG3500XT-
P1
EG3500XT-
P2
04.24 Synchronisation GGB procedure is
active
Mask: 2000h
EG3500XT-
P1
EG3500XT-
P2
04.25 Open command GGB is active
Mask: 1000h
EG3500XT-
P1
EG3500XT-
P2
04.26 Close command GGB is active
Mask: 0800h
EG3500XT-
P1
EG3500XT-
P2
Dead busbar closure requ. for GCB,MCB
or GGB
Mask: 0400h
All
4.62 Active power load share is active
Mask: 0200h
All
4.63 Reactive power load share is active
Mask: 0100h
All
Generator with a closed GCB is
requested
Mask: 0080h
All
LDSS: The Engine shall start
Mask: 0040h
All
LDSS: The Engine shall stop
Mask: 0020h
All
LDSS: The Engine shall stop, if possible
Mask: 0010h
All
LDSS: Minimum Running Time is active
Mask: 0008h
All
04.43 The LDSS function is active
Mask: 0004h
All
04.60 Critical mode postrun
Mask: 0002h
All
AUTOMATIC Run: Switch to Operating
Mode STOP
Mask: 0001h
All
891
easYgen-3000XT Series
B37574
9 Appendix
9.2.1 Protocol 5003 (Basic Visualization)