• After removing of generator rated power the new generator load level shall not lay
•
higher than 75% within the Add-on / Add-off band.
Moderate:
• After removing of generator rated power the new generator load level shall not lay
•
over 50% within the Add-on / Add-off band.
Low:
• After removing of generator rated power the new generator load level shall not lay
•
over 25% within the Add-on / Add-off band
An additional dynamic parameter (parameter
"IOP/MOP Dynamic")
with levels "Low", Moderate", and "Strong" prevents the gensets from being started and
stopped continuously if only a few gensets are in operation.
This function provides an easy calculation for the start of the next genset.
• Refer to the description of the dynamic parameters for detailed information.
•
The following parameters need to configured for this operation:
Parameter ID
Parameter text
Note
5757
IOP Dynamic
only for islanded operation
5758
MOP Dynamic
only for mains parallel operation
5767
MOP Minimum load
only for mains parallel operation
5769
MOP Hysteresis
only for mains parallel operation
5770
MOP Max. generator load
only for mains parallel operation
Table 61: Load-dependent start/stop - parameters for generator load operation
Islanded operation (IOP)
If the configured maximum generator capacity utilization is exceeded, another genset will
be added.
• PGN
real active
> P
max. load islanded
•
If the configured minimum generator capacity utilization has been fallen below, a genset
will be stopped depending on the dynamic setting (parameter
• PGN
real active
< P
min. load islanded
•
Mains parallel operation (MOP)
If the required generator load setpoint for the control at the mains interchange point
exceeds the MOP minimum load threshold (parameter
), the first genset will be
added.
• PMN
setpoint
– PMN
real
> PMOP
minimum
•