• The issue (ERRATA sheet #25 is solved: Changing from Breaker transition mode
•
"Parallel" to "Interchange" being parallel to mains and running an export power
setpoint: The MCB is opened immediately without consider the power at the
interchange point. This is now fixed. See
╚═▷ “4.4.3.1.6 Transition Modes (Breaker
for details.
• Falling into frequency and voltage droop during island operation (e.g. missing
•
member) and droop tracking is enabled. This can lead to troubles with frequency
and voltage control, if the MCB shall be synchronized. This is fixed now.
• Improved behavior during Ethernet network errors.
•
• Home screen engine (HMI) J1939 values. If a configured SPN is not available or
•
having a sensor defect, HMI indicates "---".
F
2017-09
GG
NEW Software Revision Release 1.14-4 or higher
NEW Features & Functions
• The devices are CSA certified (For details see
).
•
• The device provides now the capability to create an own Modbus address point
•
list, beginning with address 50,000. For this purpose WW provides a
TelegramMapper software tool to create customer specific DataTelegrams. This self
created DataTelegrams can be used with easYgen-XT revision 1.14 or higher. For
details see
• The device offers the capability to disable the password protection for the
•
individual interface communication channels. If the password level is disabled the
access level is set on code level 5. For details see
• For running the Remote Panel RP-3000XT with the easYgen-XT, the user can
•
dynamically switch the Remote Panel into an Full mode, Annunciator mode or Off
mode.
See menu [Parameter / Configuration / Configure HMI / Configure Remote Panel].
Corrections/Repairs
• Issue #19 described in the ERRATA sheet is solved:
•
Indication of red and amber alarm lamps of ADEC ECU7 in easYgen did not work
(ADEC ECU 7 is transmitting only one byte of DM1, eight are expected).
• Issue #18 described in the ERRATA sheet is solved:
•
Restricted to application mode GCB/L-GGB and GCB/L-GGB/L-MCB only: The
feedback of the LS-5 installed over the GGB was always recognized as closed.
• Issue #17 described in the ERRATA sheet is solved:
•
Application mode GCB/MCB together with “GCB auto unlock”: If emergency run
was active, “GCB auto unlock” could have caused simultaneous dead bus closure
of GCB and MCB if mains returned during the “GCB open pulse”. This could only
happen in parallel logic if the “GCB open time pulse” (5708) was configured higher
or same than 2 s. (This was because the mains settling time - which is shortened
to 2 s in emergency case - and the “GCB open time pulse” were mismatched.)
• Issue #16 described in the ERRATA sheet is solved:
•
Generator power factor monitoring works now even if generator measurement is
configured to 3PH3W.
• Issue #15 described in the ERRATA sheet is solved:
•
All visualization values of ADEC ECU7 are indicated now.
• Issue #13 described in the ERRATA sheet is solved:
•
MCB plausibility alarm works fine now: If MCB was not enabled (12923 = FALSE)
and start without load was active and emergency run was active, the GCB no
longer will be frequently closed and opened.
• The active power setpoint can be changed now even in island mode and with load
•
control enabled.